GenSet D diesel generator set

GenSet D-OP Series (20-2200 kVA)

GenSet D-OP is an open type diesel generator for on-site power generation, 20–2200 kVA prime, 50/60 Hz.

WhatsApp Us
ModelGenSet D-OP Series (20-2200 kVA)
CategoryGenSet D-OP
Frequency50 Hz / 60 Hz — confirm per model
FinishGrey as standard — blue or custom colours available on request
SupportSpare parts & service support in Southeast Asia, South Asia, the Balkans and Russia

At a glance

Type
Open type diesel generator
Power range
20–2200 kVA prime
Engine
Cummins diesel, 4B to QSK60
Electrical
Three-phase 50 Hz, 380/400/415/440 V
Models
34 open-frame units
Overview

Open-frame diesel gensets powered by Cummins engines for plant rooms, workshops and protected installations, covering prime ratings from 20 to 2200 kVA.

Model range

34 open-frame models covering prime ratings from 20 to 2200 kVA. Prime and standby ratings, engine options, dimensions and weights per model:

Full model table (34 models)
Model Prime Power kVA (kWe) Standby Power kVA (kWe) Cummins Engine Dimensions (L×W×H mm) Weight (kg)
D16C 20 (16) 22 (18) 4B3.9-G1 1910×775×1400 754
D24C 30 (24) 33 (26) 4BT3.9-G1 2080×790×1400 830
D32C 40 (32) 44 (35) 4BT3.9-G2 2080×790×1400 920
D44C 55 (44) 61 (48) 4BT3.9-G2 2200×800×1460 920
D60C 75 (60) 83 (66) 4BTA3.9-G11 2200×800×1450 1000
D80C 100 (80) 110 (88) 6BT5.9-G2 2475×830×1470 1280
D96C 120 (96) 132 (105) 6BTAA5.9-G2 2475×830×1470 1350
D108C 135 (108) 150 (132) 6BTAA5.9-G2 2650×890×1480 1420
D120C 150 (120) 165 (132) 6CTAA8.3-G12 2650×870×1550 1540
D144C 180 (144) 198 (158) 6CTAA8.3-G2 2750×1070×1600 1750
D160C 200 (160) 220 (176) 6CTAA8.3-G2 2750×1070×1600 1750
D176C 220 (176) 242 (200) 6ZTAA13-G3 2950×1160×1720 2170
D200C 250 (200) 275 (217) QSM11-G2 3240×1080×1650 2650
D252C 315 (252) 347 (277) QSM11-G2 3420×1160×2160 3140
D288C 360 (288) 396 (317) QSZ13-G3 3390×1380×2160 3220
D304C 380 (304) 418 (343) QSZ13-G2 3390×1380×2160 3220
D320C 400 (320) 440 (352) QSZ13-G7 3490×1160×2190 3140
D360C 450 (360) 495 (396) QSZ13-G2 3390×1380×2010 3220
D400C 500 (400) 550 (440) KTA19-G3 4058×1535×2235 4550
D460C 575 (460) 632 (520) KTAA19-G5 4058×1535×2235 4700
D500C 625 (500) 688 (550) KTAA19-G6A 4058×1535×2235 4780
D520C 660 (520) 710 (570) QSK19-G4 4058×1535×2235 4900
D600C 750 (600) 825 (670) KTA38-G9 4590×1780×2210 6500
D640C 800 (640) 880 (710) KTA38-G2B 4390×1780×2210 6700
D720C 900 (720) 990 (792) KTA38-G2A 4590×1780×2210 6850
D800C 1000 (800) 1100 (880) KTA38-G5 4390×2230×2210 6700
D880C 1100 (880) 1210 (1100) KTA38-GS 4900×2000×2240 7150
D1000C 1250 (1000) 1375 (1120) KTAA50-G3 5050×2245×2460 9140
D1100C 1375 (1100) 1513 (1210) KT50-GS8 5050×2245×2460 9400
D1200C 1500 (1200) 1650 (1320) KTAA50-GS8 5050×2245×2460 9600
D1320C 1650 (1320) 1815 (1452) QSK50-G7 5900×2180×2650 12200
D1500C 1875 (1500) 2063 (1650) QSK60-G3 5900×2250×2850 15100
D1600C 2000 (1600) 2200 (1760) QSK60-G4 5900×2250×2650 15400
D1760C 2200 (1760) 2420 (1935) QSK60-G13 6500×2500×3060 19000

Ratings are per the applicable model documentation; final selection is confirmed against your site conditions and load profile.

Technology

Technology Platform Principle

GenSet D is an industrial diesel generator set. A diesel engine drives a three-phase AC alternator, outputting 50 Hz power at 1500 rpm mechanical speed. Each model has two power ratings: Prime (continuous power) and Standby (backup power). Standby is the higher number in each row.

Open Frame Enclosure

Open frame — model suffix C, from D16C to D1760C. The engine and alternator are mounted on a steel base frame with no acoustic canopy. Advantages: good heat dissipation, easy maintenance access, and lighter weight. Open type is suited to plant room installation or any location where the building provides noise attenuation.

Engine Platform

GenSet D series uses Cummins industrial diesel engines. Engine models are listed per row in the parameter table. The range spans from 4-cylinder (4B3.9 series) to 16-cylinder (QSK60 series), covering 16 to 1760 kWe.

More technical detail

Technology Platform Principle

The core of genset selection is not the engine brand but the application definition:

The Prime/Standby power difference reflects the engine’s thermal management capability at different load duty cycles. Standby rating assumes limited annual operating hours and must not be used for continuous full-load operation. Using Standby power as the basis for continuous load selection will cause engine overheating and premature wear.

  • Prime — Genset as main power source, continuous supply. For locations where the grid is unavailable or unreliable.
  • Standby — Genset as backup, starts only on grid failure. For locations with mains power that need emergency backup.

Open Frame Enclosure

For outdoor installation or noise-sensitive environments, see the D-SL silent type series (sound-attenuated canopy) or D-CT container type series (ISO container enclosure).

Engine Platform

Suffix letters in engine model codes (G1, G2, G3, etc.) indicate different genset application calibrations. Different calibrations of the same displacement platform correspond to different power outputs and fuel consumption characteristics.

Performance Boundaries

  • Voltage — 380V, 400V, 415V, 440V, three-phase, 50 Hz. Confirm the buyer’s required voltage is among these four values.
  • Frequency — This table is 50 Hz (1500 rpm). 60 Hz (1800 rpm) is a different speed configuration, not the same machine.
  • Altitude derating — Higher altitude means lower air density, less intake air, and reduced power. Above 1,000 m, power must be derated. Confirm derating factors for the specific site.
  • High-temperature derating — Ambient temperature above the reference value reduces cooling system capacity. Power derating is required above 40°C.
  • Fuel quality — The engine has requirements for sulphur content, moisture, and impurities. Poor fuel quality shortens maintenance intervals and engine life. Confirm fuel specifications for the specific engine model.

Selection Logic

  1. Determine application type — Prime or Standby? This determines which power column to use as the selection basis.
  2. Sum the loads — List all equipment needing power, calculate total kVA. Consider starting currents (motor starting is typically 5–7× rated current).
  3. Apply derating — Correct rated power for site altitude and ambient temperature.
  4. Select model — Choose the nearest model that satisfies the load after derating.
  5. Select enclosure — Plant room with noise attenuation → Open (C). Outdoor or noise-sensitive → Silent (CC, see D-SL) or Container (see D-CT).
  6. Confirm voltage — Buyer’s required voltage must be among 380/400/415/440V.

Selection & quote checklist

  1. Total your loads
  2. Confirm noise is handled
  3. Pick prime or standby

Send this checklist with your RFQ →

Applications

Case A: Factory Standby Power

A manufacturing plant has mains supply but the grid is unstable, with several outages per month.

Case B: Mine Prime Power

A remote mine has no grid coverage and needs the genset as main power source, running 24 hours. Open type installed in the engine room.

Case C: Construction Site Temporary Power

A construction project needs 6–12 months of temporary power. Medium-sized open type mounted on a trailer for easy relocation. Noise is typically not a constraint on construction sites.

More application detail

Case D: Agricultural Irrigation

Farm operations in areas without grid coverage need reliable power for irrigation pumps and processing equipment. Open type provides cost-effective prime power where simplicity and fuel availability matter most.

Ownership & service

Energy, maintenance and service

Total Cost of Ownership

The operating cost of a diesel genset is mainly fuel. Compared to grid electricity, diesel generation cost is significantly higher per kWh. Therefore the economics of a genset depend on annual operating hours:

Annual fuel cost = Fuel consumption rate (L/h) × Annual operating hours × Diesel price.
Annual maintenance cost = Number of services × Cost per service.
Total running cost = Annual fuel cost + Annual maintenance cost.

For standby applications (tens to hundreds of hours per year), fuel cost is not the main concern — equipment reliability and start response speed matter more. For prime power applications (thousands of hours per year), fuel cost dominates running costs, and engine efficiency becomes a key selection variable.

Maintenance Cost Structure

Specific maintenance intervals are per the engine manual. The ranges above are category-general reference.

Item Typical interval Notes
Engine oil + oil filter 250–500 h First change after 50 h break-in period
Diesel filter 250–500 h Shorter with poor fuel quality
Air filter 500–1,000 h Depends on ambient dust level
Coolant 1,000–2,000 h Or annually
Valve clearance check 1,000–2,000 h Per engine manual
Overhaul 15,000–30,000 h Depends on load factor and maintenance quality

Service Support

SIND provides remote technical support (working-day response), spare parts supply by full SIND model and engine model (open and silent types share ratings and engines at the same power level, but do not share enclosure parts), and commissioning with operator and maintenance training. Specific service terms vary by region — confirm with the local authorised service provider or SIND commercial representative.

Reference data

Full specification and reference tables
Industry Typical application Enclosure Notes
Manufacturing Standby Open (in plant room) Building provides noise attenuation
Mining Prime power Open (in engine room) Continuous operation, select by Prime
Construction Temporary Open (on trailer) Mobile, noise not sensitive
Agriculture Irrigation / processing Open Areas without grid coverage
Telecom Standby Silent (see D-SL) High reliability, auto start/stop
Hospital Standby Silent (see D-SL) Life-support equipment must not lose power
  • Foundation — The genset needs a level, load-bearing foundation. Open type is typically installed on a concrete pad.
  • Ventilation — The plant room must have sufficient intake and exhaust air area. Engine heat and exhaust must be ducted outside. Insufficient intake area causes room temperature rise and power derating.
  • Exhaust — Exhaust pipe must be routed outdoors. Keep the pipe as short and straight as possible. Excessive back-pressure reduces engine power and raises exhaust temperature.
  • Fuel supply — Day tank capacity determines continuous runtime. Large loads running for extended periods need an external bulk storage tank.
  • Altitude and temperature — Above 1,000 m altitude or 40°C ambient, power must be derated. Confirm derating factors for the specific site.
SIND technical advisor

Not sure which model fits?

The SIND technical advisor helps you match capacity and configuration to your actual operating conditions before you specify.

Sizing & selection notes

  • Size for your largest motor or load start, not only the running total.
  • Choose a prime or standby rating to match how many hours per year the set will run.
  • Confirm frequency, voltage and phase for your site (for example 50 Hz or 60 Hz).
  • Check site altitude, ambient temperature and ventilation, which reduce output.
  • Allow for fuel autonomy, sound level, enclosure and parallel operation.